Skip to content
Security Alerts

CVE-2026-63586: unauthenticated root code execution in Weidmüller IE-SR-2TX-WL routers

Weidmüller IE-SR-2TX-WL industrial security routers let an unauthenticated attacker run arbitrary commands as root — a crafted username in the HTTP Authorization header is enough...

Summary

ParameterValue
CVE IDCVE-2026-63586
Alert SourceGitHub Advisory - critical vulnerability (CNA: CERT@VDE)
CVE Publication Year2026
Date Published2026-08-25
VendorWeidmüller Interface GmbH & Co. KG
ProductIE-SR-2TX-WL, IE-SR-2TX-WL-4G security routers
Affected versionsIE-SR-2TX-WL: firmware 1.52 to < V1.57; IE-SR-2TX-WL-4G: firmware 1.67 to < V1.74
Fixed versionsV1.57 (IE-SR-2TX-WL), V1.74 (IE-SR-2TX-WL-4G)
CVSS Score9.8 (Critical) — CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS Score0.5% (percentile: 42%)
CISA KEVNo
RansomwareNot confirmed
Vendor advisoryVDE-2026-083

Vulnerability Description

The web management interface of Weidmüller IE-SR-2TX-WL routers runs on a modified uhttpd server with CGI shell scripts. The username taken from the Authorization header (HTTP Basic Authentication) is inserted without sanitisation into a shell command string executed via system().

In practice an attacker with network access to the device sends an authentication header whose username contains shell metacharacters and escapes the command context. The code executes with root privileges, and the attack requires no credentials at all, because the injection happens before authentication is verified.

CERT@VDE advisory VDE-2026-083 names a concrete abuse scenario: overwriting a script served by the device’s web server to create a persistent backdoor. It survives a device reboot and does not require re-exploitation.

The same advisory covers a second flaw — CVE-2026-63587 (CVSS 8.6, SMS password authorisation bypass) — affecting the 4G variants only. After five or more invalid password attempts, SMS password authorisation is disabled and subsequent SMS commands execute without a password.

Required Actions

  1. Update the firmware: to V1.57 for IE-SR-2TX-WL and V1.74 for IE-SR-2TX-WL-4G. Weidmüller has released fixed builds for both variants.
  2. Inventory the devices — model numbers 2682590000 (IE-SR-2TX-WL), 2682560000 (IE-SR-2TX-WL-4G-EU) and 2682580000 (IE-SR-2TX-WL-4G-US-V). In OT environments these routers frequently live inside control cabinets, outside the IT asset register.
  3. Isolate the management interface from general networks. An industrial router’s web panel should be reachable neither from the internet nor from a flat office network — only from a dedicated management segment.
  4. On 4G variants, consider disabling SMS control or restricting the list of authorised numbers (CVE-2026-63587).
  5. After updating, check the device for prior compromise: modified scripts in the web server directory, unknown configuration entries, unexpected forwarding rules, and outbound connections from the router.

Who Is Affected?

Industrial plants and technical infrastructure operators using Weidmüller security routers in OT/ICS networks. Weidmüller is one of the automation suppliers present across manufacturing, energy, water utilities and building automation. The IE-SR-2TX-WL series plays the usual remote-access gateway role: connecting a control segment to the plant network or, in the 4G variant, directly to a mobile operator network for distributed sites.

That is the worst possible risk profile. The device sits precisely on the IT/OT boundary, the 4G variant can be reachable from a public carrier network, and taking it over grants root on the gateway leading to PLCs and SCADA systems.

For organisations in scope of NIS2 there is an added formal dimension: OT edge routers are part of the infrastructure subject to vulnerability management and incident reporting requirements. An unpatched remote access gateway is not only a technical risk but a gap in the compliance record.

Sources


Need help securing your systems? nFlo team offers vulnerability management and 24/7 SOC services. Contact us.

Learn More

Share:

Talk to an expert

Have questions about this topic? Get in touch with our specialist.

Sales Representative
Grzegorz Gnych

Grzegorz Gnych

Sales Representative

Response within 24 hours
Free consultation
Individual approach

Providing your phone number will speed up contact.

Want to Reduce IT Risk and Costs?

Book a free consultation - we respond within 24h

Response in 24h Free quote No obligations